VEGATOR 122 - Controller for level detection with relay output
VEGATOR 122 - Controller for level detection with relay output
Specifications
Protection rating:
IP20
Output:
2 x operating relay (SPDT)
Ambient temperature:
-20 ... 60 °C
Display & adjustment:
DIP switch
Approvals:
-ATEX / Europe
-CSA / Canada
-FM / USA
-IEC / worldwide
Explosion Protection:
-Intrinsic safety "i"
-Dust explosion protection through housing "t"
Overfill protection:
WHG
SIL qualification:
SIL2
Input:
2 x sensor input two-wire 8/16 mA
Signal input (specify):
Two-wire 8/16 mA
Signal output (specify):
Operating relay
Indication:
LED
Double channel controller for level detection
Transmission of 8/16 mA signals for level signalling (double channel)
Application areaThe VEGATOR 122 is a signal conditioning instrument for level detection for the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE with electronics version ''Two-wire“. With this instrument simple control tasks can be solved. Typical applications are monitoring functions such as overflow or dry run protection.
Advantages
- Comprehensive monitoring detects short-circuit and line break of the measuring cable and interferences in the sensor
- Simple and comfortable SIL and WHG function test by means of test key
- Simple installation through carrier rail mounting as well as detachable, coded terminals
Technical data
Input | 2 x sensor input two-wire 8/16 mA |
Output | 2 x relay output (SPDT) |
Operating voltage | 20 … 253 V AC, 50/60 Hz |
Mounting | carrier rail 35 x 7.5 acc. to EN 50022 |
SIL qualification | optionally up to SIL2 |
Refer to the link for more details: https://www.vega.com/en/home_de/products/product-catalog/signal-conditioning/controllers/vegator-122
Inquiry - VEGATOR 122 - Controller for level detection with relay output